PLATINUM SERIES RANGE
PAGE
4
OF 47
OWNER’S MANUAL 1185836 REV 8 (9/14)
SPECIFICATIONS
WARNING
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
There must be adequate clearance between the cooking equipment and combustible construction. Clearance must
also be provided for servicing and for operation.
Open-Top
Standard-Burner
Models
Open-Top
PyroMax-Burener
Models
Griddle
Models
Uniform Hot-Top
Models
Plancha
Graduated
Hot-Top
Models
Sides 10” 13” 10” 10” 6”
Back 6” 6” 12” 12” 6”
Floor* 0” 0” 0” 0” 0”
NOTICE
Local codes regarding installation vary greatly from one area to another. The National Fire Protection Association,
Inc., states in its NFPA 96 latest edition that local codes are the “authority having jurisdiction” when it comes to
installation requirements for equipment. Therefore, installations should comply with all local codes.
Southbend reserves the right to change specications and product design without notice. Such revisions do not entitle
the buyer to corresponding changes, additions, or replacements for previously purchased equipment.
Southbend appliances are intended for commercial use only, not for household use.
The installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1, Natural Gas Installation Code, CAN/CGA-B149.1, or the Propane Installation Code CAN/CGA-B149.2,
as applicable, including:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2 psi (3.45 kPa).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa).
CLEARANCES
Do NOT install sectional charbroilers or wood smokers next to combustible materials.
* Models with 6” legs or casters are suitable for installation on combustible oors.
Adequate clearance must be provided in the aisle in front of the unit to permit operation (including opening of doors
and/or removal of grease drawers, drippings trays, and/or oven racks), as well as for servicing. No additional clearance
is required for servicing as the sectional range is serviceable from the front.
Models with a convection-type oven require a minimum clearance of 2” between the motor on the back and
non-combustible construction. Care must be taken to provide adequate air circulation to prevent the motor from
overheating.
Minimum clearance from noncombustible construction is zero on the sides and back for all models (except for models
with a convection-type oven).
The high-temperature ue products ow out through the top of the ue riser of all models, and from the top of open-top
and charbroiler models. Installation under a vented hood is recommended.
Salamander broilers and cheese melters mounted on the ue riser of a sectional range may require additional
minimum clearances (see the documentation for those appliances).
SPECIFICATIONS