LP GAS HOOK-UP
-
Important Note:
An enclosure for LP gas cylinder must be vented on the level of the cylinder valve and at oor level. The
eecveness of the opening(s) for purposes of venlaon shall be determined with the LP gas supply cylinder in
place. This shall be accomplished by one of the following:
• One side of the enclosure shall be fully open; or
• For a cylinder enclosure having four sides, a top and a boom, and intended for installaon in a built-in
enclosure:
1. At least one venlaon opening shall be provided on the exposed exterior side of the enclosure lo-
cated within 5 in (1.27mm) of the top of the enclosure and unobstructed. The opening(s) shall have
a total free area of not less than 1 in²/lb (14.2 cm²/kg) of stored fuel capacity.
2. At least one venlaon opening shall be provided on the exposed, exterior side of the enclosure 1 in.
(25.4 mm) or less from the oor level and shall have a total free area of not less than ½ in²/lb (7.1
cm²/kg) of stored fuel capacity. The upper edge shall be no more than 5 in (127 mm) above the oor
level.
3. Every opening shall have a minimum dimension so as to permit the entrance of 1/8 in (3.2 mm) rod.
CAUTION:
ENCLOSURES FOR LP
HI-PRESSURE LP