Carrier 38MAQB091 Air Conditioner Cooling Area,

User Manual - Page 7

For 38MAQB091.

PDF File Manual, 10 pages, Read Online | Download pdf file

38MAQB091 photo
Loading ...
Loading ...
Loading ...
7
INSTALL ALL POWER AND INTERCONNECTING
WIRING TO OUTDOOR UNITS
1. Mount the outdoor power disconnect.
2. Run the power wiring from the main box to disconnect per
NEC and local codes.
3. Remove the field wiring cover from the unit by loosening
the screws.
4. Remove the caps from the conduit panel.
5. Connect the conduit to the conduit panel (see Fig.9).
6. Properly connect both the power supply and the control
lines to the terminal block per the connection diagram for
the appropriate unit capacity and voltage.
7. Ground the unit in accordance with NEC and local electrical
codes.
8. Use the lock nuts to secure the conduit.
9. Reinstall the field wiring cover.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Be sure to comply with local codes while running wire
from the indoor unit to the outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause the terminal to overheat or result in a unit
malfunction. A fire hazard may also exist. Therefore, be
sure all wiring is tightly connected.
S No wire should be allowed to touch the refrigerant
tubing, compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
S Connecting the cable with the conduit shall be routed
through a hole in the conduit panel.
G
Over 1.57" (40mm)
Terminal Block
Conduit panel
Conduit
Outdoor unit
A07455
Fig. 9 - Field Wiring
DRAIN CONNECTIONS
Install drains must meet the local sanitation codes.
Install the outdoor unit drain joint
Fit the seal into the drain joint, then insert the drain joint into the
outdoor unit’s base pan hole and then rotate 90
_ to securely
assemble them. Connect the drain joint with an extension drain
hose to avoid condensate from draining off the outdoor unit during
the heating mode.
Seal
Base pan hole
Drain joint
Seal
Base pan
Drain
joint
Fig. 10 - Drain Joint
Images are for illustration purposes only.
Loading ...
Loading ...
Loading ...