• Position unit for plenum installation.
• The plenum should be secured in order to support the installation of adapter callers accommodate the
installation of any duct work.
• Seal all duct work according to local codes to prevent air leakage. Ensure that filter access is
unobstructed.
• The air handler support platform should be sturdy enough to support the cabinet plus any accessory
components including filter box.
• The minimum height clearance is 14 inches(350 mm) to maintain proper air flow.
• Vibration isolators (purchased locally) must be placed between the unit and the pedestal.
• An illustration showing an example of where a vibration isolator should be added would clarify what
the installing contractor should do to properly position the isolator.
More than 6 screws (M4*25 L)
Field
Supplied Return
Plenum
More than
1 inch (25 mm)
Field Supplied
Supply Duct
Installation
Upflow Installation
CAUTION
Do not connect the screws on Front and Rear side, it may cause the filter can not be mounted.
!
ENGLISH
Installation Manual 9