VFF Vent Free Fireplace System
COMBUSTION AIR
1. Locate combustion air assembly at an exterior location
which is not likely to be accidentally blocked in any
manner. Locate assembly a min. of 12" above the snow
line to prevent blockage by snow accumulation.
2. Never mount the combustion air inlet assembly in a
garage or storage area where combustible fumes such
as gasoline might be drawn into the replace.
3. Combustion air can be drawn from the crawl space un-
der a house when an adequate supply of air is provided
by open ventilation.
4. CAUTION: Do not take combustion air from attic
space or garage space.
Figure 60 -
Basement Installation
FP2459
8' Max.
Inlet Grille in
Soft
(Overhang)
FP2460
Figure 61 -
Concrete Slab Installation
(Optional Outside Air runs)
Duct Extended
to Miss Joint
FP2461
Figure 62 -
Installation Above Basement or Crawl Space
Inside
Wall
Outside
Wall
FP2462
Figure 63 -
45° Corner Installation on Slab Floor
5. Locate air supply inlet at least 3' away from any appli-
ance vent terminal.
6. Avoid extremely long runs and numerous turns in the
duct leading from the replace to the combustion air
assembly. These conditions increase the resistance to
the free ow of air through the duct. Refer to Figures
60 through 63 for methods of installing the outside air
for combustion assemblies.
OUTSIDE COMBUSTION AIR