Gree MULTI24HP230V1CO Air Conditioner Cooling Area

User Manual - Page 16

For MULTI24HP230V1CO. Also, The document are for others Gree models: MULTI18HP230V1CO, MULTI30HP230V1CO, MULTI36HP230V1CO, MULTI42HP230V1CO

PDF File Manual, 43 pages, Read Online | Download pdf file

MULTI24HP230V1CO photo
Loading ...
Loading ...
Loading ...
Piping Height Requirements
The system piping layout must take in the constraints of vertical height on system performance.
The outdoor unit has a vertical height limit in which it can properly circulate refrigerant in the system.
INDOOR UNIT INSTALLATION
Capacity Size (BtuH) Distance ft (m)
18,000 33 (10)
24,000 33 (10)
30,000 49 (15)
36,000 49 (15)
42,000 49 (15)
Capacity Size (BtuH) Distance ft (m)
18,000 33 (10)
24,000 33 (10)
30,000 33 (10)
36,000 33 (10)
42,000 33 (10)
The maximum elevation (H1) from the bottom
of the outdoor unit to the bottom of the highest
mounted indoor units must be less than:
The maximum elevation (H2) between those
two indoor units from bottom of one unit to
bottom of the other unit must be less than:
Verify your H1 and H2 maximum elevation measurements are less than the system limits.
L2
L3
...Ln
H1
H2
15
Oil return bend
Indoor
Outdoor
20 ft.
30 ft.
Oil return bend
Oil Return Bend
When the outdoor unit is more than 30 feet above the
indoor unit, an oil return bend must be added for every
20 feet of connection pipe.
Loading ...
Loading ...
Loading ...