90
10.3.1 SINGLE ZONE:
AUTO TEST MODE
LOAD
ENABLED
Condenser (AUX A)
On for 15 seconds then OFF. Pause 2 seconds
Evaporator
On for 15 seconds then OFF. Pause 2 seconds
AUX C
On for 15 seconds then OFF. Pause 2 seconds
Comp & Cond Fan ONLY
On for 5 minutes then exit AUTO-TEST and RETURN to
NORMAL OPERATION.
NOTE: If there is a "Call for Cooling", upon return to
normal operation, the compressor and condenser fan
will remain enabled.
10.3.2 DUAL ZONE:
AUTO TEST MODE
LOAD
ENABLED
Condenser (AUX A)
On for 15 seconds then OFF. Pause 2 seconds
Evaporator Fan A
On for 15 seconds then OFF. Pause 2 seconds
Evaporator Fan B
On for 15 seconds then OFF. Pause 2 seconds
Damper A
Completes one CLOSE/OPEN/CLOSE cycle then OFF. Pause 2 seconds
Damper B
Completes one CLOSE/OPEN/CLOSE cycle then OFF. Pause 2 seconds
AUX B
On for 15 seconds then OFF. Pause 2 seconds
AUX C
On for 15 seconds then OFF. Pause 2 seconds
Comp & Cond Fan ONLY
On for 5 minutes then exit AUTO-TEST and RETURN to NORMAL OPERATION.
NOTE: If there is a "Call for Cooling", upon return to normal operation, the
compressor and condenser fan will remain enabled.
NOTE
No two loads can be on at the same time. The previous load must be
completely Off before the next load is enabled.