Mark a 9” x 9” box around the center mark (inside dimensions). Cut and frame the exterior wall to accept the
wall thimble. Install the wall thimble, on the inside of the exterior wall, shield using wood screws.
Attach the venting to the termination using sheet metal screws, for Z-Flex installations an Inca Metal Cutting’s
termination part # IMC1070A or IMC1070B shall be used. If termination is to be installed on vinyl siding use
vinyl siding standoff.
To install the termination attach the 4” exhaust to the termination and fasten with 3 #8 x ½” hex head sheet
metal screws then attach the 6” vent to the termination and fasten with 4 #8 x ½” hex head sheet metal screws,
be sure that the flex vent overlaps the termination collars a minimum of 2”. Then attach the termination to the
exterior wall using four wood screws through the holes in the corner of the vent terminal.
The next step is to apply a bead of RTV 106 to top of the 4” exhaust collar on the unit and attach the 4” vent
using screws (as described above), finally apply a bead of RTV 106 to top of the 6” vent and attach (as
described above).
Safety Cage / Cage de sécurité
A safety cage may be required on low terminations. Please check with your local safety authority.
Une cage de sécurité peut être nécessaire de faibles terminaisons. S'il vous plaît vérifiez auprès de votre
autorité de sécurité locale.
Safety Cage
12.50
9.00”
12.50”
9.00”
ø
8”
ø
6”