Choosing an Installation Site
•Beforechoosingtheinstallationsite,obtainuserapproval.
1. Indoor unit
CAUTION
•Whenmovingtheunitduringorafterunpacking,makesuretoliftitbyholdingitsliftinglugs.Donotexertanypressureon
otherparts,especiallytherefrigerantpiping,drainpipingandangeparts.
Wearprotectivegear(suchasgloves)wheninstallingtheunit.
•Ifyouthinkthehumidityinsidetheceilingmightexceed86°F(30°C)andRH80%,reinforcetheinsulationontheunitbody.
Useglasswoolorpolyethylenefoamasinsulationsothatthethicknessismorethan0.4in(10mm)andtsinsidetheceiling
opening.
•Optimumairdistributionisensured.
•Theairpassageisnotblocked.
•Condensatecandrainproperly.
•Theceilingisstrongenoughtobeartheweightoftheindoorunit.
•Afalseceilingdoesnotseemtobeatanincline.
•Sufcientclearanceformaintenanceandservicingisensured.
•Pipingbetweentheindoorandoutdoorunitsiswithintheallowablelimits.
(Refertotheinstallationmanualfortheoutdoorunit.)
•Theindoorunit,outdoorunit,powersupplywiringandtransmissionwiringisat
least3.3ft(1m)awayfromtelevisionsandradios.Thispreventsimage
interferenceandnoiseinelectricalappliances.(Noisemaybegenerated
dependingontheconditionsunderwhichtheelectricwaveisgenerated,even
ifa3.3ft(1m)allowanceismaintained.)
Use suspension bolts to install the unit. Check whether or not the
ceiling is strong enough to support the weight of the unit. If there is
a risk that the ceiling is not strong enough, reinforce the ceiling
before installing the unit.
(Installationpitchismarkedonthecartonboxforinstallation.Refertoittocheck
forpointsrequiringreinforcing.)Selectthe*Hdimensionsuchthatadownward
slopeofatleast1/100isensuredasindicatedinDrain Piping Work”.
•Theinstallationpitchislistedonthepackingmaterial,andshouldbechecked
whendecidingwhethertoreinforcethelocationornot.
Control box
Maintenance
space
12 (300)
or more
13/16 (20) or more
100 (2500)
or more
*H=
9-1/2 (240)
or more
7-7/8
(200)
Ceiling
Floor surface
(unit : in (mm))
If there is
no ceiling
Select the signal receiver mounting location according to the
following conditions:
•Installthesignalreceiver,whichhasabuilt-intemperaturesensor,nearthe
intakeventwherethereisconvectionofairanditcangetanaccuratereading
oftheroom’stemperature.Iftheintakeventisinanotherroomortheunit
cannotbeinstalledneartheintakeventforanyotherreason,installit5ft
(1.5m)abovetheooronawallwherethereisconvection.
•Inordertogetanaccuratereadingoftheroom’stemperature,installthesignal
receiverinalocationwhereitisnotexposeddirectlytocoldorhotairfromthe
airdischargegrilleortodirectsunlight.
•Sincethereceiverhasabuilt-inlightreceptortoreceivesignalsfromthe
wirelessremotecontroller,donotmountitinalocationwherethesignalmay
beblockedbyacurtain,etc.
Air outlet grille:
Wooden or plastic grille is recommended
because condensation may occur
depending on humidity conditions.
CAUTION
Ifthesignalreceiverisnotinstalledinalocationwherethereisconvectionofair,itmaybeunabletogetanaccuratereading
oftheroom’stemperature.
01_EN_3P297301-4D.indd 3 5/8/2017 5:10:21 PM