Hydrostatic pressure test
Pressure test before attaching gas piping or electrical supply.
1. Plug any necessary boiler tappings or openings.
2. Do not use gauge supplied with boiler for pressure testing.
Install gauge with appropriate range.
3. Fill boiler with water. Vent all air. Test steam boilers between
45 - 55 psi. Test water boilers at 1-1/2 times maximum work-
ing pressure.
Do not leave boiler unattended. A cold water fill could
expand and cause excessive pressure, resulting in severe
personal injury, death or substantial property damage.
4. Verify gauge pressure is maintained. Check for leaks. Repair
if found.
Leaks must be repaired at once. Failure to do so can
cause boiler damage, resulting in substantial property
damage.
Do not use petroleum-based sealing compounds in
boiler system. Severe damage to boiler will result,
causing substantial property damage.
5. Drain boiler and repair leaks if found.
6. Retest boiler after repairing leaks.
7. Remove plugs from any tappings that will be used for controls
and accessories. Refer to Table 4 and Figure 5.
/N INITIALSTARTUP CHECKFORLEAKSIN THE SYSTEM PIPING)F
found, repair at once.
Installation of flue baffles (EGH only)
1. Bend the two (2) tabs on the flue baffle approx. 90 degrees in
opposite directions.
2. Slide flue baffles (notch down and to the back) in between
each section.
The installer must install all flue baffles for proper
boiler operation.
&IGURE Boiler tappings (see Table 4)
4ABLE Control tapping (see Figure 5)
Prepare tKe EoLler (continued)
Tapping
Size
EG, PEG & EGH
Steam Boilers
EG & PEG only
Water Boilers
C
¾”
3UREHW\SHORZZDWHUFXWRII 3UREHW\SH/:&2ZKHQXVHG
D
¾”
Drain Drain
E
¾”
Safety valve Safety relief valve
G
¾”
3OXJJHG
3LSLQJWRFRPSUHVVLRQWDQNRU
auto air vent
H
½”
*DXJHJODVVDQGRURSWLRQDOORZZDWHU
cutoff
&RPELQDWLRQSUHVVXUH
WHPSHUDWXUHJDXJH
J
Ǫ´
Tri cock tappings
3OXJJHGRQ)ORDWW\SH
/:&2
L
½”
6LSKRQSUHVVXUHJDXJHKLJKOLPLW
3UREHW\SH/:&2
&RPELQDWLRQSUHVVXUH
WHPSHUDWXUHJDXJH
P
(EGH
Only)
1
)ORDWW\SHORZZDWHUFXWRIISUHVVXUHOLPLW
FRQWURODQGSUHVVXUHJDXJHRUORZZDWHU
FXWRIIDQGIHHGHUFRPELQDWLRQRUORZ
ZDWHUFXWRIIDQGSXPSFRQWURO
––
S
1 ½”
¾”
(note 1)
6NLPWDSSLQJ
––
/LPLWFRQWURO
/LPLWFRQWURO
Notes:
$YDLODEOHRQVSHFLDOUHTXHVWRQO\ZKHQWDQNOHVVKHDWHULVVSHFL¿HG
/LPLWFRQWURODQGVXSSO\SLSLQJPXVWEHRQWKHVDPHHQGRIWKH(*+ERLOHU
:KHQDQLQWHUQDOW\SHZDWHUKHDWHULVLQVWDOOHGXVHWKHWDSSLQJLQWKHKHDWHUIRUDQ
DGGLWLRQDORSHUDWLQJFRQWURO
&IGUREA EGH - Flue baffles
Installation of optional indirect water
heater
1. For a boiler ordered with internal type indirect water heater,
remove heater opening cover plate (water boilers – round
plate on left side; steam boilers – rectangular plate on front).
)NSTALLHEATERSASSHOWNONPAGE$ONOTOVERTIGHTEN
studs and nuts - damage to the gasket can occur.
EG
&
PEG SERIES 5
s
EGH SERIES 5 GAS-FIRED BOILERS — BOILER MANUAL
%HQGWDEVRQHDFKSODWHWR
NHHSIURPIDOOLQJWKURXJK
ÀXHZD\