Part Number 550-141-186/0914
s)NSTALLATIONs3TART5Ps-AINTENANCEs0ARTS
10b
Maintenance — minimum schedule
"
Repair leaks at
once
No petroleum-
based chemicals
#HECKFORLEAKSINBOILERANDPIPING)FFOUNDREPAIRATONCE
2. Visually inspect pilot and burner flames. Refer to Check pilot burner flames and Check
main burner flame, Section 10c
PAGE
3. Visually inspect venting system for blockage, deterioration or leakage. Refer to Inspect
venting system, Section 10c
PAGE
Leaks must be repaired at once. Failure to do so can cause damage to boiler,
resulting in substantial property damage.
Do not use petroleum-based sealing compounds in boiler system. Severe
damage to boiler will result.
$
Follow Annual shutdown procedure, Section 10cPAGE
#HECKTHATBOILERAREAISFREEFROMCOMBUSTIBLEMATERIALSGASOLINEANDOTHERmAMMABLE
VAPORSANDLIQUIDS
2. Check for and remove any obstruction to flow of combustion or ventilation air.
#HECKRELIEFVALVE2EFERTORELIEFVALVEMANUFACTURERSINSTRUCTIONSONRELIEFVALVETAG
2. Test low water cutoff, if used. Blowdown if low water cutoff is float type. Refer to low water
cutoff manufacturer’s instructions.
!NNUALSERVICECALLBYAQUALIlEDSERVICEAGENCY
2. Check burners and flueways and clean if necessary. Refer to Clean boiler heating surfaces
and Clean main burners, Section 10cPAGE
3. Follow procedure,
Section 8, Placing boiler in operation, page 26.
4. Visually inspect pilot and burner flames. Refer to Check pilot burner flames and Check
main burner flame, Section 10c
ONPAGE
5. Visually inspect venting system for blockage, deterioration or leakage. Refer to Inspect
venting system, Section 10c,
PAGE
6. Visually inspect base insulation. Refer to
Inspect base insulation, Section 10cPAGE
7. Check operation of low water cutoff, if used, and additional field-installed controls. Refer
to control manufacturer’s instructions.
8. Check that boiler area is free from combustible materials, gasoline and other flammable
VAPORSANDLIQUIDS
#HECKFORANDREMOVEANYOBSTRUCTIONTOmOWOFCOMBUSTIONORVENTILATIONAIR
,UBRICATECIRCULATORSIFREQUIREDPERCIRCULATORMANUFACTURERSINSTRUCTIONS