Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping
connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent
burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all
burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Step 3: Flare pipe ends

1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign
materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. 
sure they are facing in the right direction,
because you can’t put them on or change their

Flare nut
Copper pipe
4. Remove PVC tape from ends of pipe when

5. 
The end of the pipe must extend beyond the

dimensions shown in the table below.

Outer Diameter
of Pipe (mm)
A (mm)
Min. Max.
Ø6.35 (Ø 0.25”) 0.7 (0.0275”) 1.3 (0.05”)
Ø9.52 (Ø 0.375”) 1.0 (0.04”) 1.6 (0.063”)
Ø12.7 (Ø 0.5”) 1.0 (0.04”) 1.8 (0.07”)
Ø16 (Ø 0.63”) 2.0 (0.078”) 2.2 (0.086”)
Ø19 (Ø 0.75”) 2.0 (0.078”) 2.4 (0.094”)
Flare form
Pipe
A
6. 
7. 

8. 
inspect the end of the pipe for cracks and

Step 4: Connect pipes
When connecting refrigerant pipes, be careful not
to use excessive torque or to deform the piping in

pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the
minimum bending radius is 4 inches.
4in
Radius
Refrigerant Piping Connection