Weil-McLain LGB COMMERCIAL GAS BOILER LGB-20

User Manual - Page 18

For LGB COMMERCIAL GAS BOILER LGB-20.

PDF File Manual, 40 pages, Read Online | Download pdf file

LGB COMMERCIAL GAS BOILER LGB-20 photo
Loading ...
Loading ...
Loading ...
Part Number 550-141-186/0914

LGB
3ERIES'AS&IRED"OILER"OILER-ANUAL

Pipe the header at least 24 inches above the boiler water line.
7EIL-C,AINRECOMMENDSUSINGABOILERFEEDSYSTEMWITHTHEPUMPOPERATEDBYALEVELCON-
TROLLERONTHEBOILER7EIL-C,AINDOESNOTRECOMMENDUSINGACONDENSATERETURNSYSTEMON
which the pump is operated by a receiver-mounted float switch. Level controls (Section 6)
MUSTBEMOUNTEDONSAMESIDEOFBOILERASTHERETURNPIPINGANDEQUALIZER
Install a blowdown valve in tapping
C1 or C2 (see Figures 11a and 11bPAGESAND
SIZEDPER!3-%#ODE
Models LGB-4 through LGB-12USEvBLOWDOWNVALVE
Models LGB-13 through LGB-23USEvBLOWDOWNVALVE
See Figure 200AGEFORMULTIPLESTEAMBOILERPIPING
*4
Steam boiler piping for
LGB-4 through LGB-12
(single riser)
*3
Steam boiler piping for
LGB-13 through LGB-23
(riser each end)
3b
Pipingsteam boilers
Improper piping systems and/or undersized piping can contribute to erratic
boiler operation and possible boiler damage. The piping must be installed
as illustrated, using the recommended minimum pipe sizes.
Minimum Recommended Pipe Sizes
Boiler
Model
Number
Riser
A
Header
H
Equalizer
J
LGB-4 ––
LGB-8
4” 4” 2”
LGB-9 ––
LGB-11
5” 5” 2½”
LGB-12
6” 6” 2½”
Minimum Recommended Pipe Sizes
Boiler
Model
Number
Risers
A B
Header
H
Equalizer
J
LGB-13 ––
LGB-15
4” 4” 6” 4”
LGB-16 ––
LGB-19
5” 5” 6” 4”
LGB-20 ––
LGB-23
6” 6” 8” 4”
OR
Reducing from header
to equalizer - alternate
piping methods.
DO NOT reduce the
header in the
horizontal piping.
1
186-17a
Loading ...
Loading ...
Loading ...