INSTALLATION MANUAL - Page 12

For RXS24LVJU. Also, The document are for others Daikin models: RXS09LVJU, RXS12LVJU

Loading ...
Loading ...
Loading ...
11
English
Facility Setting
(cooling at low outdoor temperature)
This function is designed for facilities such as equipment or computer rooms. It is never to be used in a
residence or ofce where people occupy the space.
Cuttingjumper4(J4)onthecircuitboardwillexpandtheoperationrangedownto14°F(–10°C).Howeveritwillstopif
theoutdoortemperaturedropsbelow–0.4°F(–18°C)andstartbackuponcethetemperaturerisesagain.
1
2
3
S70
S40
S2
S90
J5
J4
J3
Cut J4 with nippers
or a similar tools.
CAUTION
•Iftheoutdoorunitisinstalledwheretheheatexchangeroftheunitisexposedtodirectwind,provideawindbreakwall.
•Intermittentnoisesmaybeproducedbytheindoorunitduetotheoutdoorfanturningonandoffwhenusingfacilitysettings.
•Donotplacehumidiersorotheritemswhichmightraisethehumidityinroomswherefacilitysettingsarebeingused.
Ahumidiermightcausedewcondensationfromtheindoorunitoutletvent.
•Cuttingjumper4(J4)setstheindoorfantaptothehighestposition.Notifytheuseraboutthis.
01_EN_3P300674-1B.indd 11 8/28/2012 5:51:00 PM