14
SlimFit
®
Series 2
commercial condensing gas-fired water boiler
- User’s Information Manual
Part number 550-100-562/0321
Maintenance procedures — PERIODICALLY
Perform DAILY procedures
plus the following additional
procedures . . .
Test the low water cutoff
1. Remove the boiler jacket door liing the jacket door
up and o.
2. Locate the low water cut-o on the burner end of heat
exchanger opposite igniter side.
3. Press the TEST buon.
Hold the button for at
least 5 seconds
. Any shorter time will result in an
automatic reset instead of a manual reset.
4. e green STATUS light should change to red, indicat-
ing a low water condition.
5. e SlimFit boilers control will shut down the boiler
on manual reset.
6. The control display will flash red as shown in
Figure9,page8.
7. Select MANUAL RESET to reset the control
8. e boiler should return to normal operation.
If the low water cuto fails to cause a manual
reset lockout condition, immediately turn
o all power to the boiler and contact your
boiler technician.
If the low water cuto SERVICE light is on,
contact your service technician immediately.
9. Replace the jacket door.
Check control date and time
1. Check the time shown on the control display (see
Figure5,page6).
2. If time is incorrect, set the correct date and time as
shown in Figure5,page6.
Figure 11 Low water cutoff
Loading ...
Loading ...