Installation Instructions (cont'd)
Filling the Water Heater
&CAUTION I
Never usethiswater heater unlessit mscompletelyfilledw_l
water.Topreventdamageto the tank, the tankmustbefilledI
with water. Water must flow from the hot water faucet I
I beforetorn ng ON' gasto thewater heater.
To fill the water heater with water:
Close the water heater drain valve by turning the handle to
the right (clockwise). The drain valve is on the lower front of
the water heater.
Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open
when the water heater is in use.
To insure complete filling of the tank, allow air to exit by
opening the nearest hot water faucet. Allow water to run
until a constant flow is obtained. This will let air out of the
water heater and the piping.
Check all new water piping for leaks. Repair as needed.
Venting
_WARNING
VENT DAMPERS- Any ventdamper,whether it isoperated
thermallyor otherwisemustbe removedifitsuseinhibitsprop-
er drafting ofthewater heator,
Thermally OperatedVent Dampers:Gas-firedwater heaters
havingthermalefEciencyineacessof80%mayproducea rela-
lowfluegastemperature.Suchtemperaturesmaynotbe
high enough to properly open thermally operated vent
dampen. Thiswouldcausespillageoffluegasesandmaycause
carbonmonoxidepoisoning.
dampersmustbearevidenceofcertiEcntionascomplying
with the latestedition ofAmerican NationalStandardANSI
Z21.68 (ANSI 7.21.66& 67,respectively,coverelectricallyand
mechanicallyactuatedventdampers);Beforeinstallationofany
ventdamper,consultyourlocalSea_ ServiceCenterorthe gas
utilityforfurtherinformation.
AWARNING
To insureproper venting of this gas-firedwater heater,the
correctvent pipediameter mustbe utilized.Anyadditionsor
deletions ofothergasappliancesona commonvent with this
water heater mayadverselyaffectthe operationof the water
heater,Consultthe localSearsServiceCenter or gasutilityif
anysuchchangesare planned.
For proper venting in certain installations, a larger diameter vent
pipe may be necessary. Due to great variances in installations,
unforeseeable by the manufacturer of the water heater, you must
consult your gas company to aid you in determining the proper
venting for your water heater from the vent tables in the latest
edition of the National Fuel Gas Code ANSI Z223.1, also
referred to as NFPA 54.
Check the venting system for signs of obstruction or deterioration
and replace if needed.
The combustion and ventilation air flow must not be obstructed.
AWARNING . I
Obstructed or deteri,o_tedventsystemsmaypresentasenous
healthrisk or asphyxiation.
Place the draft hood legs in the receiving holes on the top of
the water heater. The legs will snap in the holes to give a tight
fit.
Place the vent pipe over the draft hood. With the vent pipe in
position, drill a small hole through both the vent pipe and
draft hood. Secure them together with a sheet metal screw.
DRAFT HOOD _ VENT_L t
,"_ _ "_I_SCRF'LW_--J DRAFT HOOD
J L VENT TO OUTDOORS OR
_ CHIMNEY
DRAFT
A WARNING I
The water heaterwith draft hoedinstalledmust be properlyI
ventedto a chimneywhich terminates outdoors. Never oper-
ate the waterheaterunlessit isventedto the outdoorsandhasI
adequateairsupplyto avoidrisksofimproperoperation, explo-
son or asplrtxiadon.
AWARNING ]
The vent pipefromthrust beno lessthan the|
diameter of the draft hoodoutlet on the water heater,and|
must slopeupwardto the chimneyat least¼inchper linear|
foot /
13