Ideal 61-076 Vol-Con® Solenoid Voltage/Continuity Tester

User Manual - Page 6

For 61-076. Also, The document are for others Ideal models: 61-080, 61-067, 61-065

PDF File Manual, 24 pages, Read Online | Download pdf file

61-076 photo
Loading ...
Loading ...
Loading ...
6
Service, and Replacement Parts:
For replacement parts or to inquire about service
information contact Technical Support:
1-877-201-9005 or visit our website
www.idealindustries.com.
Specifications:
VAC Ranges: 120V, 240V, 480V, 600V AC.
VDC Ranges: 120V, 240V, 600V DC
Volts Accuracy: Relative indication only
Continuity: LED lights at <500kΩ
Response time of 100ms.
Frequency: Operates at 25-60 Hz
Overload 1000VDC/750VAC rms.
protection:
Operating 32°F to 122°F
Environment: (0 to 50°C)(<70% humidity)
Storage Temp.: -4°F to 140°F (-20 to 60°C)
(<80% humidity)
Batteries:
Models 61-080 & 61-076 only
(4) 1.5V (61-201, IEC LR44)
Battery Life: 200 hours typical.
Accessories Test Leads, (4) Batteries,
included: Operating Manual
Dimensions: 7.2”H x 2.4”W x 1.5”D
[183H x 61W x 38D]mm
Weight: 8.0 oz (227g)
Safety: UL 61010B-1, CAT III-600V
Double Insulation
Instrument has been evaluated and complies
with insulation category III (overvoltage
category III). Pollution degree 2 in accordance
with IEC-644. Indoor use.
Clamp Meter
10DB
Loading ...
Loading ...
Loading ...