Conditioned Air Supply Drive Belts - Your KwiKool KIB120 models moves air
over the evaporator coil to remove heat and moisture from the conditioned space by
way of a motor attached to a blower wheel, this wheel turns by way of a pulley and belt
system. Inspect/adjust these belts every 60 days of operation, replace as needed.
Failure to maintain the drive belts will cause low performance, coil freezing or in extreme
cases damage to the blower/motor in the event of a belt breaking. The belts are located
in the left side evaporator access door as you face the control panel. When adjusting
the belts, adjust the tension using the base adjustment screw. Never adjust the sheave
(pulley) as it can cause damage to your system and/or make the system have poor
performance.