Movincool CLASSIC10 Portable Air Conditioner Cooling Area,

User Manual - Page 13

For CLASSIC10.

PDF File Manual, 31 pages, Read Online | Download pdf file

CLASSIC10 photo
Loading ...
Loading ...
Loading ...
13
INSTALLATION (cont.)
Fire Alarm Control Panel Connection
(Input Signal Terminal E+ and E-)
The controller is equipped with a normal open input signal, which can be
connected directly from the fire alarm control panel. This input signal terminal
should only be connected to a close or open dry contact signal. When receiving
the signal from the fire alarm control panel, the unit turns off and does not turn back
on until it has been RESET.
Connecting Fire Alarm Control Panel to Controller
1. Remove service panel from the rear of the unit.
2. Squeeze the inner latches and push out the black cap from inside the panel.
3. Use recommended warning signal wire size from 16 AWG to 26 AWG for a
solid wire, or 16 AWG to 22 AWG for a stranded wire with ring terminal for #6
stud size.
4. Connect the fire alarm device to terminal E+ and E- according to its polarities.
Cap
Latch
UNIT TERMINAL
OUTPUT SIGNAL
FIRE ALARM DEVICE
E+
E-
L+
L-
OPEN DRY CONTACT