Napoleon S20I

User Manual - Page 10

For S20I.

PDF File Manual, 80 pages, Read Online | Download pdf file

S20I photo
Loading ...
Loading ...
Loading ...
W415-2797 / D / 05.07.21
EN
10
2.0 installation planning
Clean all ashes out of the inside of the existing fireplace opening. Make sure that the chimney and fireplace are free
of cracks, loose mortar, creosote deposits, blockage or other signs of deterioration. If necessary, have any repair
work done by a qualified professional before installing the insert.
Do NOT remove bricks or mortar from the fireplace. In case of an outside air inlet or ash dump, fill with fiberglass
insulation. Adhere to minimum clearances as illustrated.
Combustible material must not protrude more than 1" (25mm) to the side of the insert or between the mantel and
the top of the insert.
MINIMUM CLEARANCES
A
Sidewall
16" (406mm)
B
Mantel
30" (762mm)
C
Top facing
22" (559mm)
D
Side facing
10" (254mm)
E
Hearth (front)
22" (559mm)
F
Minimum hearth
thickness
1” (25mm)
G
Hearth (side) 8” (203mm)
H
In front of insert
48" (1219mm)
MINIMUM EXISTING
FIREPLACE DIMENSIONS
I
Width (rear)
25 7/8" (657mm)
J
Width (front)
K
Height (front)
22" (559mm)
L
Height (rear)
M
Depth
14" (356mm)
N
Hearth width
41 3/8" (1051mm)
O
Facing width
45 3/8" (1153mm)
P
Facing height
42 5/8" (1083mm)
Q
Mantel
50 5/8" (1286mm)
2.1 minimum clearance to combustibles
HEARTH EXTENSION / FLOOR
PROTECTION:
Must be non-combustible and extend 22"
(559mm) in front of the insert and 8" (203mm)
on both sides with a minimum thickness of 1"
(25mm) and a thermal conductivity factor (K)
0.84.
O
P
Q
J
M
K
L
I
N
SIDE WALL
D
E
H
G
A
B
C
F
Clearances can be reduced with shielding
acceptable to local authorities. Reduced
installation must comply with NFPA 211 or
CAN/CSA-B365.
Loading ...
Loading ...
Loading ...