Do not place any combustible material within 4’
(1.2 m) of the front of the unit.
The clearance between the ue pipe and a wall
are valid only for vertical walls and for vertical ue
pipe.
The chimney connector must not pass through an
attic or roof space, closet or similar concealed
space, a oor, or a ceiling.
For Canadian installations, where passage through
a wall, or partition of combustible construction
is desired, the installation must conform to CAN/
CSA-B365.
A ue pipe crossing a combustible wall must have a
minimum clearance of 18” (457.2 mm).
To reduce ue clearances from combustible
materials, contact your local safety department.
SPECIAL MOBILE HOME REQUIREMENTS (USA ONLY)
WARNING! - Do not install in a sleeping room.
CAUTION! - The structural integrity of the mobile home oor, wall, and ceiling/roof must be maintained.
In addition to the previously detailed installation requirements, mobile home installations must meet the following
requirements:
The space heater is to be connected to a factory-built chimney conforming to CAN/ULC-S629, Standard for
650°C Factory-Built Chimneys.
The heater must be permanently attached to the oor (see “Securing Appliance’s On A Pedestal To The Floor”
section of this manual.
The heater must be electrically grounded to the steel chassis of the mobile home with 8 GA copper wire using
a serrated or star washer to penetrate paint or protective coating to ensure grounding.
When moving your mobile home, all exterior venting must be removed while the mobile home is being
relocated. After relocation, all venting must be reinstalled and securely fastened.
Outside air is mandatory for mobile home installation. See your dealer for purchasing.
Check with your local building ofcials as other codes may apply.
Only use the specied components listed in this manual for this unit. The use of components that are not meant
for this unit can cause unsafe conditions.
COMBUSTION AIR ASSEMBLY INSTRUCTIONS (MOBILE HOME INSTALLATIONS - REQUIRED)
This appliance requires a source of combustion air. If your home is of tight construction or has negative pressure
problems, you will need an outside source of air. Below is a list of possible indicators that a source of outside
combustion air may be required.
Key Dimensions Inch mm
D Backwall to Stove 17 432
E Sidewall to Stove 26 661
F Wall to corner (Angled Installation) 18 458
G Ceiling Height 84 2134
H Backwall to Flue 19 483
J Sidewall to Flue 35 889
H
D
J
E
CLEARANCE TO WALLS
Side wall
Backwall
F
F
Side wall
Backwall
CORNER INSTALLATION
CLEARANCE TO WALLS
Ceiling
CORNER INSTALLATION
CLEARANCE TO
WALLS & CELING
G
D
H
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during installation
of the stove. Refer to the provided tables: