OPTIONAL FEATURES
TREATED EVAPORATOR AND CONDENSER COILS
When airborne contaminants are a problem for air conditioning applications, acrylic and heresite coated
coils are recommended to guard against pitting and corrosion. Call factory for details.
CONDENSER DUCT
If a longer, 12" or 16" diameter duct is needed on the condenser discharge, 10 ft. flexible ducts may be
coupled or weaved together to your desired length. The following chart
CEILING PANEL/DUCT KIT ASSEMBLY
A 12 inch diameter (Model 2OAC/2OACH12-18-24-36) and 16"
diameter (Model 2OAC/2OACH60) flexible duct kit assembly
extends to vent condenser air or to draw condenser return air
from the ceiling when a condenser return air plenum is used. It
comes with a 2' X 2' lay in ceiling panel/collar assembly for
venting into the plenum area above the false ceiling, plus a duct
collar to attach the duct to the unit. Installation can be completed
by following these simple steps:
1) Slip one end of the duct over the lay in ceiling panel/collar
assembly and the other over the unit duct
collar.
2) Clamp or screw duct to lay-in ceiling
panel/collar assembly and unit duct collar.
3) Place the 2' X 2' lay-in ceiling panel in
the false ceiling directly above the unit.
4) Screw duct collar to unit with three
screws provided.
8
2x2 Lay-in ceiling panel
Flexible Duct
Duct Flange (attaches to
unit)
Duct flange provided on 3 and 5 ton units.
Model
Ceiling Kit
Round Flexible
Duct Size Diameter
Length
Fits
2OAC12
2OACH12
Fits
2OAC18-24
2OACH18-24
Fits
2OAC36
2OACH36
Fits
2OAC60
2OACH60
CK-12
Size/Fits
12 inch
8 feet
Yes Yes Yes
No
CK-16
Size/Fits
16 Inch
8 feet
No No No
Yes
Maximum
Equivalent Feet
(add 6 feet for each 90° bend)
(ESP)
25
(.20)
40
(.25)
80
(.50)
80
(.50)
Loading ...