Checking your system
Verify System is running correctly
Once your system has been
Filled, Purged, and Pressurized,
verify that both Primary and
Secondary pumps are running.
Check your supply and return
pressures. Your supply gauge
should be the same as what you
pressurized it to. You should see
about a 5-7 PSI differential on
the return gauge when the sys-
tem is running. Verify the boiler
is energized and providing heat.
Set your flow on the manifold.
Each loop should be at .5 to .75
GPM. (Based on 1/2” Pex Tubing)
Manifold/Emitter flow may vary depending
on Pex Size, length and other factors.