Hydro Smart HS120CON-NG 120K Microboiler

User Manual - Page 26

For HS120CON-NG.

PDF File Manual, 60 pages, Read Online | Download pdf file

HS120CON-NG photo
Loading ...
Loading ...
Loading ...
Installation Manual
Page
26
Follow all code requirements
of the local authority on
condensate neutralizers
and whether or not they are
required for the installation.
-CONDENSATE DRAIN-
-Pressure relief valve-
The micro-boiler has a high-temperature shutoff switch built in as a standard safety feature (called
a Hi-Limit switch) therefore a "pressure only" relief valve is required. If you are using Hydro Smart
pre-built panels the pressure relief valve will be on the primary(boiler) loop of the Master Panel and an
additional pressure relief valve may not be needed, check local codes.
This micro-boiler does not come with an approved pressure relief valve.
An approved pressure relief valve must be installed on the hot water outlet.
The pressure relief valve must conform to ANSI Z21.22 or CAN 1-4.4 and installation must follow
local codes.
The discharge capacity must be at least 120,000 BTH/h.
The pressure relief valve needs to be rated for a maximum of 75 psi (0.5 MPa).
Attach the discharge piping for the pressure relief valve and run the end of the tube to within 6
inches (152 mm) from the oor. This discharge tube must allow free and complete drainage without
any restrictions.
If the pressure relief valve installed on the micro-boiler discharges periodically, this may be due to
a defective thermal expansion tank, defective pressure relief valve, or it could be signs of internal
scale build up.
The pressure relief valve must be manually operated periodically to check for correct operation.
No valves may be placed between the relief valve and the micro-boiler.
The micro-boiler does not include a built-in condensate neutralizer cartridge for reducing the pH
level of condensate water. If local codes dictate that condensate must be neutralized prior to
drainage, a condensate neutralizer must be installed. An accessory Neutralizer assembly is sold
separately.
In the absence of applicable local codes and regulations, the manufacturer recommends that
condensate be disposed of into a standard drain. Connect a drain tube from the condensate drain
port (shown below) located on the bottom of the micro-boiler to a standard drain.
Condensate drain port
Installation