Installation
HP Installatio
n and User Instructions R00918
-10 09/15
Page
28
4.8 Connection of
Secondary Return
A secondary return port is installed on
the 210, 250 and 300L cylinders. For
cylinders that do not have a dedicated
secondary return connection, it is
possible to install a secondary return
by connecting a swept - T to the cold
water inlet of the cylinder (see Figure
9).
The secondary return pipe should
incorporate a check valve and a WRAS
approved circulation pump; timer and
thermostat to be provided separately.
Where secondary return circuits are
used, then an additional expansion
vessel may be required.
The secondary return loop must avoid:
- stagnant water in long pipe runs
- long waiting times at draw off point
for hot water
- undue water wastage
To minimise the energy consumption of
the secondary return circuit and to
ensure reliable operation it is important
to consider:
- the control of the circulation pump to
be time and temperature controlled
- the secondary return circuit pipe
work to be insulated
- the secondary return pump to be of
suitable material and specification
Figure 9: Secondary return loop
To Taps
From Taps
Secondary
Return
Swept-T
HW Outlet