INSTALLATION
CLEARANCES TO COMBUSTIBLES
Figure 1 - Minimum Clearance for
Combustible to Wall and Ceiling
Figure 2 - Clearances to Combustibles
WARNING: You must main-
tain the minimum clearances. If
you can, provide greater clear-
ances from oor, ceiling, and
adjoining wall. Measure from
outermost point of heater.
WARNING: Do not pack re-
quired air spaces with insulation
or other materials.
Carefully follow the instructions below. This
replace is designed to sit on an approved
mantel base or installed in an existing re-
place. When rebox is installed directly on
carpeting, tile or other combustible material,
the rebox must be installed on a metal or
wood panel extending the full width and depth
of the replace.
7" Min
7" Min
42" Min.
Side
Wall
Side
Wall
Ceiling
Minimum Clearances For Side
Combustible Material, Side Wall
and Ceiling
IMPORTANT: You must maintain minimum
wall and ceiling clearances during installation.
The minimum clearances are shown in Figure
1. Measure from outermost point of replace.
A. Clearances from outermost point of re-
place to any combustible side wall should
not be less than 7".
B. Clearances from the replace to the ceiling
should not be less than 42".
BUILT-IN FIREPLACE INSTALLATION
WARNING: Do not allow any
combustible materials to overlap
the rebox front.
WARNING: Do not allow
combustible or noncombustible
materials to cover any necessary
openings like louvered slots.
WARNING: Never modify or
cover the louvered slots on the
front of the rebox.
Built-in installation of this replace involves
installing replace into a framed-in enclosure.
This makes the front of the replace ush
with wall. If installing a built-in mantel above
the replace, you must follow the clearances
shown in Figure 2.
3/4" Clearance to Facia at Nailing Flange
1
3
/
8
" Clearance to Sides, Back and Top
Note: Height of fireplace opening at facia to be
32 ½" (PC32VFC) and 36 ¾" (PC36VFC).
35
1
/
2
" (PC32VFC) 43
1
/
2
" (PC36VFC)
44
3
/
8
" (PC32VFC) 44
3
/
4
" (PC36VFC)