MODEL OWC1211 OWC1811 OWC2412 OWC3612 OWC3632 OWC6012 OWC6032
Nominal Cooling Capacity1
13,780 18,840 23,950 36,100 36,100 60,100 60,100
Voltage 208/230/3 208/230/1 208/230/3
Cooling Amps5 10.5/5.3 12.0/6.2 8.6 13.0 9.4 20.7 14.8
Cooling Watts5 1050 1400 1990 3000 3000 5350 5350
E.E.R. 13.1 13.5 12.3 12.0 12.0 11.3 11.3
In Rush Current (AMPS) 79 92.6 64.6 109.6 103.4 183.1 134.2
Fuse/Breaker (AMPS) 15 15 20 20 20 30 20
Plug Type 5-15P 5-15P 6-20P 6-20P L15-20P 6-30P L15-20P
Compressor HP 1 1 1/2 2 3 3 5 5
Compressor RLA 9.3 11.4 8.3 17.9 11.4 28.0 20.0
Compressor LRA 58 65 49 88 77 169 123
Evaporator CFM2 400 600 810 1310 1310 2200 2200
Evap Motor HP 1/15 1/5 1/3 1/2 1/2 1 1
Evap Motor Watts 200 210 350 375 375 550 550
Condenser Water Flow at 60°F inlet GPM 0.75 1.10 1.55 2.20 2.20 5.50 5.50
at 85°F inlet 3.0 4.5 6.0 9.0 9.0 15.0 15.0
Condenser Coil Pressure Drop-PSI .40 .40 .20 .40 .40 .40 .40
Water Valve Pressure Drop-PSI
Water Valve Connection4
Drain Connection
Condensate Pump Head (Standard)
Sound Level3 52 57 60 62 62 69 69
R-22 Charge Oz. 19 22 24 36 36
(A) Height with Casters 31 1/2
(D) Height without Casters 28 1/2
(B) Width 20 1/8
(C) Depth 13 1/8
Net Weight 120 165 170 225 225 350 350
Shipping Weight 125 175 180 235 235 385 385
Shipping Volume 9 18 18 21 21 36 36
208/230/60/1
20 Feet
1Nominal Capacity is net BTU/HR at 80°F DB/67°F WB return air or 85°F EWT to 95°F LWT (#GPM/Ton). 2CFM with free discharge. 3Sound Pressure, dB at 5 feet Com. Config.
Specifications subject to change without notice.
115/60/1 or 208/230/60/1
3/8 MF
2.0
4Size 3/8 valve used on model 12, 18, 24 (3/8 MF Fitting) 5/8 valve used on models 36 and 60 (5/8 MF fitting)
5Amps & Watts at 208 volts
3/8 MF 5/8 MF
68
37 1/2 47 52 1/4
34 1/2 42 1/2 46 1/2
28 1/4
13
15 1/2 39
24 1/4