<GL71/80>
Outdoor unit
Remote controller
Remote controller holder
Only use the remote controller provided with the unit.
Do not use other remote controllers.
If two or more indoor units are installed in proximity to one another, an indoor unit that is not intended to be operated may respond to the remote controller.
Before operation: Insert the power supply plug into the power outlet and/or turn the breaker on.
Installing the remote controller batteries
The operation indicator lamp shows the operation state of the unit.
| Indication | Operation state | Room temperature |
The unit is operating to reach the set temperature | About 2°C or more away from set temperature | |
The room temperature is approaching the set temperature | About 1 to 2°C from set temperature | |
Demand Response mode Page 10 | — |
ALighted
Blinking
Not lighted
AUTO mode (Auto change over)
The unit selects the operation mode according to the difference between the room temperature and the set temperature. During AUTO mode, the unit changes mode (COOL↔HEAT) when the room temperature is 2°C away from the set temperature for more than 15 minutes.
Note:
Auto Mode is not recommended if this indoor unit is connected to a MXZ type outdoor unit. When several indoor units are operated simultaneously, the unit may not be able to switch operation mode between COOL and HEAT. In this case, the indoor unit becomes standby mode (Refer to table of Operation indicator lamp).
COOL mode
Enjoy cool air at your desired temperature.
Note:
Do not operate COOL mode at very low outside temperatures (less than -10°C). Water condensed in the unit may drip and wet or damage furniture, etc.
DRY mode
Dehumidify your room. The room may be cooled slightly.
Temperature cannot be set during DRY mode.
HEAT mode
Enjoy warm air at your desired temperature.
FAN mode
Circulate the air in your room.
Note:
After COOL/DRY mode operation, it is recommended to operate in the FAN mode to dry inside the indoor unit.
When the remote controller cannot be used...
Emergency operation can be activated by pressing the emergency operation switch (E.O.SW) on the indoor unit.
Each time the E.O.SW is pressed, the operation changes in the following order:
Operation indicator lamp
Set temperature : 24°C
Fan speed : Medium
Horizontal vane : Auto
Note:
If a power failure occurs or the main power is turned off during operation, “Auto restart function” automatically starts operation in the same mode as the one set with the remote controller just before the shutoff of the main power. When timer is set, timer setting is cancelled and the unit starts operation when power is resumed.
If you do not want to use this function, please consult the service representative because the setting of the unit needs to be changed.
Press to select fan speed. Each press changes fan speed in the following order:
Press to select airflow direction. Each press changes airflow direction in the following order:
Press to select horizontal airflow direction. Each press changes airflow direction in the following order:
(AUTO) .........The vane is set to the most efficient airflow direction. COOL/ DRY/FAN: horizontal position. HEAT: position (5).
(Manual) .......For efficient air conditioning, select the upper position forCOOL/DRY, and the lower position for HEAT. If the lower position is selected during COOL/DRY, the vane automatically moves to the horizontal position after 0.5 to 1 hour to prevent any condensation from dripping.
(Swing) .........The vane moves up and down intermittently
<GL71/80 only>
Pressto start LONG operation.
Press again to cancel LONG operation.
<GL71/80 only>
Press during COOL or HEAT mode Page 5 start POWERFUL operation.
Fan speed : Exclusive speed for POWERFUL mode
Horizontal vane : Set position, or downward airflow position during AUTO setting
Press again to cancel POWERFUL operation.
Press again to cancel i-save operation.
Example of use:
Press during COOL mode page 5 to start ECONO COOL operation.
The unit performs swing operation vertically in various cycles according to the temperature of airflow.
Press again to cancel ECONO COOL operation.
Swing airflow (change of air flow) makes you feel cooler than stationary airflow. The set temperature and the airflow direction is automatically changed by the microprocessor. It is possible to perform cooling operation with keeping comfort. As a result energy can be saved
Note:
E.g.: Runs at 24°C from waking up to leaving home, and runs at 27°C from getting home to going to bed on weekdays.
Note:
Note: The simple ON/OFF timer setting is available while the weekly timer is on. In this case, the ON/OFF timer has priority over the weekly timer; the weekly timer operation will start again after the simple ON/OFF timer is complete.
Note: The saved settings will not be cleared when the weekly timer is turned OFF.
Note:
When all days of the week are selected to view the settings and a different setting is included among them, will be displayed
Demand response
This unit has demand response capability which is compliant with AS/NZS 4755.3.1.
To activate this function, you need to make a contract with remote agents such as electric supply company, then this unit should be connected to Demand response enabling devise (DRED). For further information, consult your dealer.
Demand response represents the automated alteration of an electrical product’s normal mode of operation in response to an initiating signal originating from or defined by a remote agent.
This unit supports 3 Demand Response Modes (DRMs)
DRM | Description of operation in this mode | Operation indicator lamp
|
DRM 1 | Compressor off The air conditioner does not perform cooling or heating operation during the demand response event. | Upper lamp is lighted. Lower lamp blinks. |
DRM 2 | The air conditioner continues to perform cooling or heating operation during the demand response event, but the electrical energy consumed by the air conditioner in a half hour period is not more than 50% of the total electrical energy that would be consumed if operating at the rated capacity in a half hour period. | |
DRM 3 | The air conditioner continues to perform cooling or heating operation during the demand response event, but the electrical energy consumed by the air conditioner in a half hour period is not more than 75% of the total electrical energy that would be consumed if operating at the rated capacity in a half hour period. |
Note:
DRM cannot be invalidated or changed manually.
However, you might not feel cool or warm enough as DRM is prioritized.
Instructions:
Back side of air filter
Clean every 3 months:
When dirt cannot be removed by vacuum cleaning:
Every year:
GL25/35/42/50/60: MAC-408FT-E
GL71/80: MAC-2350FT-E
Note: Do not apply excessive force to the fan or fan guard.
Even if these items are checked, when the unit does not recover from the trouble, stop using the air conditioner and consult your dealer.
Symptom | Explanation & Check points |
Indoor Unit | |
The unit cannot be operated. | Is the breaker turned on? Is the power supply plug connected? Is the ON timer set? Page 8 |
All LED lamps on the indoor unit are blinking. | Are the horizontal vanes installed correctly? Page 11 |
The horizontal vane does not move. | Are the horizontal vane and the vertical vane installed correctly? Page 11 Is the fan guard deformed? |
The unit cannot be operated for about 3 minutes when restarted. | This protects the unit according to instruc tions from the microprocessor. Please wait. |
Mist is discharged from the air outlet of the indoor unit. | The cool air from the unit rapidly cools mois ture in the air inside the room, and it turns into mist. |
The swing operation of the HORIZONTAL VANE is suspended for a while, then restarted. | This is for the swing operation of the HORI ZONTAL VANE to be performed normally. |
The airflow direction changes during operation. The direction of the horizontal vane cannot be adjusted with the remote controller. | When the unit is operated in COOL or DRY mode, if the operation continues with air blowing down for 0.5 to 1 hour, the direction of the airflow is automatically set to horizon tal position to prevent water from condensing and dripping. In the heating operation, if the airflow tem perature is too low or when defrosting is be ing done, the horizontal vane is automatically set to horizontal position. |
The operation stops for about 10 minutes in the heating operation. | Outdoor unit is in defrost. Since this is completed in max. 10 minutes, please wait. (When the outside temperature is too low and humidity is too high, frost is formed.) |
The unit starts operation by itself when the main power is turned on, but isn’t received sign from the remote control ler. | These models are equipped with an auto re start function. When the main power is turned off without stopping the unit with the remote controller and is turned on again, the unit starts operation automatically in the same mode as the one set with the remote control ler just before the shutoff of the main power. Refer to “Auto restart function” Page 5 . |
In COOL/DRY mode, when the room temperature reach es near the set temperature, the outdoor unit stops, then the indoor unit operates at low speed. | When the room temperature rises and the outdoor unit turns on, the indoor fan starts running according to the settings on the remote controller. |
The indoor unit discolors over time. | Although plastic turns yellow due to the influ ence of some factors such as ultraviolet light and temperature, this has no effect on the product functions. |
Outdoor Unit | |
The fan of the outdoor unit does not rotate even though the compressor is running. Even if the fan starts to rotate, it stops soon. | When the outside temperature is low dur ing cooling operation, the fan operates intermittently to maintain sufficient cooling capacity. |
Water leaks from the outdoor unit. | During COOL and DRY operations, pipe or pipe connecting sections are cooled and this causes water to condense. In the heating operation, water condensed on the heat exchanger drips down. In the heating operation, the defrosting operation makes ice forming on the outdoor unit melt and drip down. |
White smoke is discharged from the outdoor unit. | In the heating operation, vapor generated by the defrosting operation looks like white smoke. |
Symptom | Explanation & Check points |
Remote controller | |
The display on the remote controller does not appear or it is dim. The indoor unit does not respond to the remote control signal. | Are the batteries exhausted? Page 4 Is the polarity (+, -) of the batteries correct? Page 4 Are any buttons on the remote controller of other electric appliances being pressed? |
Does not cool or heat | |
The room cannot be cooled or heated sufficiently. | Is the temperature setting appropriate? Page 5 Is the fan setting appropriate? Please change fan speed to High or Super High. Page 6 Are the filters clean? Page 11 Is the fan or heat exchanger of the indoor unit clean? Page 11 Are there any obstacles blocking the air inlet or outlet of the indoor or outdoor unit? Is a window or door open? It may take a certain time to reach the setting temperature or may not reach that depending on the size of the room, the ambient tempera ture, and the like. |
The room cannot be cooled sufficiently. | When a ventilation fan or a gas cooker is used in a room, the cooling load increases, resulting in an insufficient cooling effect. When the outside temperature is high, the cooling effect may not be sufficient. |
The room cannot be heated sufficiently. | When the outside temperature is low, the heating effect may not be sufficient. |
Air does not blow out soon in the heating operation. | Please wait as the unit is preparing to blow out warm air. |
Poor cooling or heating performance. | Do you have an arrangement with your elec tric company for Demand Response? |
Airflow | |
The air from the indoor unit smells strange. | Are the filters clean? Page 11 Is the fan or heat exchanger of the indoor unit clean? Page 11 The unit may suck in an odor adhering to the wall, carpet, furniture, cloth, etc. and blow it out with the air. |
Sound | |
Cracking sound is heard. | This sound is generated by the expansion/ contraction of the front panel, etc. due to change in temperature. |
“Burbling” sound is heard. | This sound is heard when the outside air is absorbed from the drain hose by turning on the range hood or the ventilation fan, making water flowing in the drain hose to spout out. This sound is also heard when the outside air blows into the drain hose in case the outside wind is strong. |
Mechanical sound is heard from the indoor unit. | This is the switching sound in turning off/on the fan or the compressor. |
The sound of water flowing is heard. | This is the sound of refrigerant or condensed water flowing in the unit. |
Hissing sound is sometimes heard. | This is the sound when the flow of refrigerant inside the unit is changed. |
Timer | |
Weekly timer does not oper ate according to settings. | Is the ON/OFF timer set? Page 8, 9 Transmit the setting information of the weekly timer to the indoor unit again. When the infor mation is successfully received, a long beep will sound from the indoor unit. If information fails to be received, 3 short beeps will be heard. Ensure information is successfully received. Page 9 When a power failure occurs and the main power turns off, the indoor unit built-in clock will be incorrect. As a result, the weekly timer may not work normally. Be sure to place the remote controller where the signal can be received by the indoor unit. Page 3 |
The unit starts/stops the operation by itself. | Is the weekly timer set? Page 9 |
WHEN YOU THINK THAT TROUBLE HAS OCCURRED
In the following cases, stop using the air conditioner and consult your dealer.
WHEN THE AIR CONDITIONER IS NOT GOING TO BE USED FOR A LONG TIME
When using the air conditioner again:
Avoid installing the air conditioner in the following places.
If you have any questions, consult your dealer.
Reference file: Mitsubishi MSZ-GL71VGD SPLIT-TYPE Air Conditioner
Additionally, the document applies to other Mitsubishi models: MSZ-GL25VGD, MSZ-GL35VGD, MSZ-GL42VGD, MSZ-GL50VGD, MSZ-GL60VGD, MSZ-GL80VGD